IQ, OQ and PQ explained
Installation, operational and performance qualification ask three questions in order: is it installed as specified, does it operate, does it perform?
Qualification builds evidence in layers. Each stage has a protocol with pre-defined acceptance criteria, an execution record, and a report approved before the next stage begins — or with a documented justification where stages overlap.
For a temperature-controlled chamber or room
- IQ: equipment identity, utilities, sensor positions, calibration certificates for controllers and monitoring sensors, drawings, manuals, software version.
- OQ: control at set points across the range, alarm function, door-opening recovery, power-failure behaviour, empty-chamber temperature distribution.
- PQ: loaded mapping under routine operating conditions, over a duration that captures normal use, against the product-derived acceptance criteria.
The mapping study is therefore not a separate activity bolted onto qualification; it is the substance of OQ and PQ for temperature-controlled spaces.
The three questions, and the evidence each one needs
| Stage | The question | Typical evidence |
|---|---|---|
| IQ | Is it installed as specified? | Equipment identity and serial numbers, utilities connected and verified, sensor positions against drawings, calibration certificates for controlling and monitoring sensors, software version, manuals and spares, as-built drawings |
| OQ | Does it operate across its ranges? | Control at each set point, alarm challenge to the limit with escalation, door-opening recovery, power-failure and restart behaviour, empty-room temperature distribution |
| PQ | Does it perform in routine use? | Loaded mapping over a duration that covers the normal operating cycle, with real product, real door traffic and the monitoring system running |
Where teams actually get into trouble
Three errors account for most of it. The first is running PQ on an empty room because the product had not arrived. An empty room has unobstructed airflow and flatters the equipment; the loaded study is the one that supports a storage decision, and a PQ performed empty places no limit on how full the room may later be packed.
The second is using the room's own control sensor as the qualification sensor. Ask the instrument that is holding the set point whether the set point is being held and it will always say yes. Qualification sensors are independent, calibrated, and placed where product sits, not where the controller sits.
The third is treating the stages as paperwork to be signed in sequence rather than gates. Starting OQ before IQ is closed means testing operation of an installation nobody has confirmed; when OQ then fails, the investigation has to consider installation as a cause, and half the evidence is not yet recorded.
Overlapping stages, done properly
Annex 15 allows stages to be combined or to overlap where justified, and for small equipment a combined IQ/OQ is normal and sensible. What it does not allow is the justification being left implicit. Write down which activities were merged and why, and confirm that no test lost its prerequisite — a calibration certificate that IQ would have checked is still needed before an OQ test relies on that sensor.
The mapping study is not an extra
- Empty-room distribution is an OQ test: it characterises the equipment without the confounding effect of load.
- Loaded mapping is the PQ: it is the performance evidence, and the duration has to cover the operating cycle rather than a convenient weekend.
- The monitoring sensor positions come out of the mapping, so the monitoring system cannot be finally qualified before the mapping is analysed.
- The worst-case locations the study identifies become the reference points for every periodic review that follows.
A useful test of a qualification package: could a reader who has never seen the room tell, from the documents alone, where the warmest location is and why the monitoring sensor is where it is? If not, the mapping has not been connected to the rest.
Frequently asked questions
- What is DQ?
- Design qualification: documented verification that the proposed design is suitable for the intended purpose, performed before purchase or build.
- Must PQ use real product?
- Annex 15 allows simulated product where justified; the justification and the simulation's limitations should be recorded.
References
- [1]EudraLex Volume 4, Annex 15: Qualification and Validation (2015)
- [2]WHO Technical Supplement 8 to TRS 961 Annex 9: Temperature mapping of storage areas (2015)
General technical guidance written against the cited sources. It is not regulatory or legal advice and does not replace the applicable standard, guideline or a qualified reviewer's judgement.
Have a question on this topic?
Ask ValiTrac AI and see the evidence and calculation behind the answer.
Ask ValiTrac AIFree calculator: Protocol builder
Build a draft IQ, OQ and PQ protocol for a cold room, chamber, autoclave or vehicle — document control, the test list that suits that equipment, record tables and approval blocks. It will not write your acceptance criteria, and says so.
Open the calculatorRelated articles
EU GMP Annex 15: the qualification stages explained
Annex 15 sets URS, DQ, FAT/SAT, IQ, OQ and PQ as a sequence that builds evidence a system is fit for its intended use, with requalification after changes.
Qualifying a stability or climatic chamber
Chambers are qualified for temperature and humidity uniformity, stability and recovery — with acceptance criteria tied to the ICH conditions they will run.